Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: saleshelp@tripplite.com
View online Owner's manual for Tripp Lite SmartPro Rackmount SMX1000RT2U UPS or simply click Download button to examine the Tripp Lite SmartPro Rackmount SMX1000RT2U guidelines offline on your desktop or laptop computer. Tripp Lite's SMART1500RM2U intelligent, line-interactive sine wave rack/tower uninterruptible power supply prevents data loss, downtime and equipment damage due to power outages, voltage fluctuations and transient surges. User Manual: Accessories for the Tripp Lite SmartPro Intelligent Rack Mount UPS: 36' IEC Power Cord (4 Pack).
Tripp Lite SMART1000RM1U 1000VA / 1kVA / 800 watt line interactive, sine wave UPS system offers complete power protection for critical network applications in a highly efficient 1U total rack/tower configuration. Simultaneous-use network management interfaces include USB, RS-232 and optional SNMP/Web accessory card. Get Tripp Lite SMART1500LCD Digital UPS Systems Owner's Manual. Get all Tripp Lite manuals! Sign up to create an account Facebook Twitter. By clicking Create Account, you agree to the Company’s. Do not open your UPS for any reason. There are no user. This manual contains instructions and warnings that should be followed during the installation, operation and storage of all Tripp Lite UPS Systems. Failure to heed these warnings may affect your warranty. Statement of Intended Use Tripp Lite Medical-Grade UPS Systems are intended to support and protect non-medical.
Model #: SMART2200NET
Smart Pro UPS System - Intelligent, line-interactive battery backup for network and telecommunications System
Highlights
2200VA / 2.2kVA line interactive, extended-run tower UPS
Maintains 120V nominal output over an input range of 87 to 140V
Network communications supported via 3 DB9 ports (1 serial / 2 contact
closure)
Input: NEMA 5-15P (120V 15A) / Output: 6 NEMA 5-15R (120V)
2 year product warranty / $250,000 Ultimate Lifetime Insurance (USA, Puerto
Rico & Canada only)
Description
Tripp Lite's SMART 2200NET intelligent, line interactive large tower UPS system protects servers, networking accessories and telecommunications
equipment from blackouts, voltage fluctuations and transient surges. Large internal batteries offer 27 minutes half load runtime and 11 minutes fully
loaded. Runtime is expandable with optional BP24V28-2U (limit 1) and BP24V70-3U external battery packs. 2200VA/1700 watt power handling
capability supports a variety of networking, telecom and other sensitive electronic applications. Includes 6 protected outlets. Supports remote
monitoring of UPS and site power conditions via built-in RS-232 enabled monitoring port, plus standard UPS monitoring via 2 built in contact closure
ports. Includes PowerAlert UPS monitoring and unattended shutdown software with complete cabling. Built-in audible alarm and front panel LEDs
indicate line power, battery power, battery charge level, load level, plus voltage regulation status. Network grade AC surge suppression protects
equipment from damage and performance problems resulting from transient surges. Two year warranty with $250,000connected equipment
insurance.
Applications
Ideal for the protection of communication equipment including: routers, hubs, switches, IP-PBX, Traditional PBX and Key/Hybrid Telephone Systems. Also ideal for the protection of data processing equipment such as fileservers, workstations and other sensitive devices requiring clean, continuously regulated output power. Extended runtimes are available using additional external battery packs.
Package Includes
SMART 2200NET UPS System
PowerAlert Software and three 6 foot network cables
Warranty information
Instruction manual
Features
SMART 2200NET line interactive UPS offers battery derived AC output during power outages, voltage regulation during brownouts and overvoltages, plus network-grade AC surge suppression
2200VA/1700 watt power handling capability supports a variety of networking, telecom and other sensitive electronic devices
Large internal batteries offer runtimes of 27 minutes at half load (1100VA/850 watts) and 11 minutes at full load (2200VA/1700 watts) Runtime is further expandable with optional external BP24V28-2U (limit 1) and BP24V70-3U (multi-pack compatible) battery packs (output VA is derated as external battery packs are added, see specifications)
Automatic Voltage Regulation (AVR) circuits maintain 120V nominal output over an input voltage range of 87-140V
Includes 6 fully protected NEMA 5-15R outlets with 2 single outlet load banks that can be individually powered off and back on again via software interface
PowerAlert UPS monitoring and unattended shutdown software enables configurable network broadcast messaging, email notification, event logging and running user defined script commands
Offers simultaneous monitoring of up to 3 directly connected devices through included DB9 contact closure and RS-232 enabled interfaces, or the monitoring of any number of additional servers over IP with included PowerAlert monitoring software
In addition to the contact closure monitoring of on battery, low battery and power restored messaging, built-in RS-232 interface supports messaging of UPS and line power status, including AC line voltage, DC battery voltage and remaining battery capacity
Supports activate self-test and UPS output power control for delayed or immediate reboot of connected equipment
Diagnostic LEDs (indicate 17 performance conditions)
UL (USA), cUL (Canada), NOM (Mexico), FCC Class A (Business) Listed $250,000 Ultimate Lifetime Insurance (USA & Canada Only)
Specifications
SYSTEM OVERVIEW
Voltage compatibility | 120V AC |
Frequency | 60 Hz |
compatibility | |
OUTPUT | |
Output VA | 2200 |
Output watts | 1700 |
Output nominal | 120V AC |
voltage | |
Output voltage | LINE MODE: Sine wave line voltage 120V (-13% / +5%) |
regulation | BATTERY MODE: PWM sine wave output 120V +/-5% |
Output frequency | LINE MODE: Passes line frequency of 60Hz +/-10% |
regulation | BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz |
Outlet quantity / type | 6 NEMA 5-15R |
Customized load | 2 individually controlled single-outlet banks supports reboot of selected items and load shedding to increase battery |
management | runtime for the most critical of loads. |
receptacles | |
Overload protection | Via 20A input breaker |
INPUT | |
Maximum input amps | 15A, 1770 watts |
Input connection type | NEMA 5-15P |
Input cord length | 8 ft., 12 gauge |
Recommended | 20A 120V |
Electrical Service | |
BATTERY | |
Full load runtime | 11 minutes (2200VA) |
Half load runtime | 27 minutes (1100VA) |
Expandable battery | Supports extended runtime with optional BP24V28-2U (limit 1) and BP24V70-3U (multi-pack compatible) external |
runtime | battery pack. Capacity de-rates to 1600VA / 1280 watts with 1 external BP and 1250VA / 800 watts with 2 external BPs |
DC system voltage | 24 V DC |
Typical battery | 3-6 years, depending on usage |
lifespan | |
Battery recharge rate | 2-4 hours to 90% |
VOLTAGE REGULATION | |
Voltage regulation | Line interactive UPS offers 2 boost levels of brownout correction and a single level of overvoltage adjustment to |
description | maintain usable, computer grade output without consuming battery power. |
Overvoltage correction
Direct pass through
Brownout correction
Severe brownout correction
Input voltages between 127 and 140V AC are reduced by 12%
Tripp Lite Smart Pro Ups User Manual Pdf
Input voltages between 110 and 127V AC are passed through unchanged
Input voltages between 95 and 105V AC are boosted by 10%
Input voltages between 87 and 94V AC are boosted by 22%
Includes 5 front panel LEDs to indicate BATTERY CHARGE LEVEL, AC LINE POWER STATUS, VOLTAGE REGULATION STATUS, UPS LOAD LEVEL and BATTERY LOW / REPLACE information
Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.
Includes 2 front panel switches — one on/standby power switch and one dual function 'alarm cancel' / 'self test' button, plus 1 rear panel system enable switch
SURGE / NOISE SUPPRESSION
AC surge | 480 joules |
suppression | |
AC suppression | Instantaneous |
response time | |
EMI / RFI AC noise | Yes |
suppression | |
PHYSICAL | |
Shipping weight (lbs) | 87 |
Shipping weight (kg) | 39.5 |
Shipping | 22.25 x 12.75 x 16.5 |
Dimensions (HWD/in) | |
Shipping | 57.2 x 32.4 x 42 |
Dimensions | |
(HWD/cm) |
Unit weight (lbs)
Unit weight (kg)
Unit Dimensions (HWD/in)
Unit Dimensions (HWD/cm)
Tripp Lite Smartpro Net Ups
Material of construction
Form factors supported
Cooling method
Receptacle Color
ENVIRONMENTAL
80
36.3
17 x 9 x 12.5
41.9 x 22.9 x 31.1
Polycarbonate
Tower
Convection
Black
Relative Humidity
Storage Temperature
Operating
Temperature
Line mode BTU/hr. (Max.)
Battery mode
BTU/hr. (Max.)
COMMUNICATIONS
0 to 95%, non-condensing
+5 to +122 degrees Fahrenheit, -15 to +50 degrees Celsius
+32 to +104 degrees Fahrenheit, 0 to +40 degrees Celsius
148.2
502.6
Network monitoring Includes 3 built-in DB9 monitoring ports, 1 enabled with RS-232 data communications and 2 with standard contact port closure communications. All interfaces support on battery, low battery and power restored messaging. RS-232 enabled
port adds data regarding AC
Software and cabling Includes PowerAlert UPS monitoring software for all common network and standalone operating systems. included
LINE / BATTERY TRANSFER
Transfer time from | 2-4 milliseconds |
line power to battery | |
mode | |
Low voltage transfer | Switches to battery power as line voltage decreases to 87 volts or less |
to battery power | |
High voltage transfer | Switches to battery power as line voltage increases to 140 volts or higher. |
to battery power | |
SPECIAL FEATURES | |
Appearance | Black tower UPS |
BATTERY PACK ACCESSORY (optional) | |
Battery Pack | BP24V28-2U (limit 1) and BP24V70-3U (multi-pack compatible) |
Accessory (optional) | |
CERTIFICATIONS | |
Certifications | Tested to UL1778 (USA), cUL (Canada), FCC Class A (emissions), NOM (Mexico) |
WARRANTY | |
Product Warranty | 2 year product warranty |
Period | |
Connected | $250,000 connected equipment insurance (USA / Canada only) |
Equipment Coverage | |
Optional Coverage | 3-5 year warranties, plus next day and on-site warranty coverage available for select opportunities. Contact Tripp Lite |
for additional information |
Related Items
Extended Warranties
WEXT3-2200-3000 | 3-Year Extended Warranty - For Smart Line-Interactive and Online Tower or Rack models, | Qty: [optional] |
2200-3000VA | ||
WEXT5-2200-3000 | 5-Year Extended Warranty - For Smart Line-Interactive and Online Tower or Rack models, | Qty: [optional] |
2200-3000VA or less | ||
External Battery Packs | ||
BP24V28-2U | External Battery Pack for UPS System (limit 1) | Qty: [optional] |
BP24V70-3U | External Battery Pack for UPS System (multi-pack compatible) | Qty: [optional] |
Power Distribution | ||
RS-1215 | Tripp Lite Power Strip - Multiple outlets wherever you need them | Qty: [optional] |
PDU1215 | Basic PDU / Power Distribution Unit - Safe, reliable power distribution for critical networking | Qty: [optional] |
equipment | ||
Surge Protectors | ||
DTEL2 | Network Surge Suppressor - Essential protection for data and communication lines | Qty: [optional] |
DNET1 | Network Surge Suppressor - Essential protection for data and communication lines | Qty: [optional] |
DCATV | Network Surge Suppressor - Essential protection for TV/VCR coaxial lines | Qty: [optional] |
More information, including related products, owner's manuals, and additional technical specifications, can be found online at www.tripplite.com/en/products/model.cfm?txtModelID=40.
©2009 Tripp Lite. All Rights Reserved.